FirePause
Home About Us Products Blog Cart 0 Contact
Training Certifications Contact
Back to Q&A Community
Hydrants & Sprinklers

What are the pressure switch settings for fire jockey pumps?

Our jockey pump control panel in Chakan shows cut-in and cut-out settings. At what pressure should the jockey pump start and stop automatically?
Responses 1
🧯
FirePause Expert Team Fire Safety Expert
2 months, 2 weeks ago
In a typical system designed for 7.0 kg/cm² operating pressure:
Jockey Pump Cut-in: 6.2 kg/cm² (Starts when pressure drops due to minor leakage).
Jockey Pump Cut-out: 7.0 kg/cm² (Stops when line is fully pressurized).
Main Electric Pump Cut-in: 5.5 kg/cm² (Starts when flow exceeds jockey capacity, indicating active fire). The main pump must be stopped manually according to codes.

💬 Submit a Response

Your expertise can help other community members. Please maintain code references and guidelines.