What is the standard wall thickness for fire hydrant MS piping?

We are laying MS pipes for yard hydrants at our warehouse site in Bhiwandi. What class of thickness is required under IS 1239?
Responses 1
🧯
FirePause Expert Team Fire Safety Expert
2 months, 2 weeks ago
Under IS 1239, fire hydrant pipes must be Mild Steel Heavy Class (C Class) pipes. The wall thickness for a standard 100mm (4-inch) pipe should be 5.4mm, and for a 150mm (6-inch) pipe, it should be 5.4mm to 6.0mm to withstand hydrostatic testing pressures (15 kg/cm²) and prevent external soil corrosion over the years.