Hydrants & Sprinklers 2 months, 3 weeks ago
What are the pressure switch settings for fire jockey pumps?

Our jockey pump control panel in Chakan shows cut-in and cut-out settings. At what pressure should the jockey pump start and stop automatically?

Verified Safety Expert Answer

In a typical system designed for 7.0 kg/cm² operating pressure: - Jockey Pump Cut-in: 6.2 kg/cm² (Starts when pressure drops due to minor leakage). - Jockey Pump Cut-out: 7.0 kg/cm² …

Hydrants & Sprinklers 2 months, 3 weeks ago
What is the standard flow rate for fire hydrant pumps in high-rises?

We are buying a new electric fire pump for our commercial tower in Worli. What is the required flow rate in Liters Per Minute (LPM) under MCGM rules?

Verified Safety Expert Answer

For high-rise commercial structures exceeding 24 meters in height, the standard main electric fire pump must have a minimum discharge flow rate of 2280 LPM (approx. 600 GPM) at a …